lindab | smoke Duct Dimensions LKRSS b L a Minimum dimensions: 150x150 mm Maximum dimensions: 1900x1700 mm Non CE marked Dimensions: From 1900x1700 to 3000x1700 mm Description Straight duct, stiffened with transverse corrugations, which reduces the risk of noise generation. Larger dimensions have stiffening internal rods. Ducts are normally supplied with a strong joining profile RJFP at each end. The product is CE marked according to EN 12101-7 and used in a rectangular smoke control system - single com- partment (see declaration of performance). Classification according to EN13501-4 150×150 up to 1250×1000 mm 1250×1000 up to 1900×1700 mm 1900 × 1700 up to 3000 × 1700 mm E 600 120 (h o -v e ) S 1500 single E 600 120 (h o ) S 1500 single Non CE marked Ordering example Product Largest side Smallest side Length LKRSS 500 a b L 300 1500 4 We reserve the right to make changes without prior notice 2020-02-24