lindab | dampers and measure units UltraLink Controller Factory settings Min. flow velocity [m/s] Max. flow velocity v(nom) [m/s] Analog in range [V] Analog out 1 range [V] Analog out 2 range [V] Default Value Parameter 0 On request Value Parameter 0,7 7 10 or 15 2–10 2–10 Flow Flow 0–10 0–10 Flow Flow 2–10 Damper pos. 0–10 2–10 0–10 Damper pos. Temp. Temp. Wiring For wiring with premounted cable: red white yellow brown grey green blue pink 24V GND +B -A GND AO1 AO2 AIN Red White Yellow Brown Grey Green Blue Pink 24V , power supply (AC G, DC +) * GND , power supply (AC G0, DC -) * +B , connection for Modbus via RS485 -A , connection for Modbus via RS485 GND , ground (system neutral) AO1 , analog output AO2 , analog output AIN , analog input *) When using AC terminal 1 (G) should have system poten- tial and terminal 2 (G0) should be system neutral. FTCU 2 DUCT-MC Identification number 17.11.002 Lindab reserves the right to make changes without prior notice 2021-02-16