lindab | dampers and measure units Damper with flow meter FMDU Δ p [Pa] 80 100 125 160 200 250 315 400 500 630 Ød 1 Technical data Flow graph for balancing The curves show the flow, q, as a function of the pressure dif- ference in the measurement nozzles. Flow data for dimen- sioning differs from this graph. Ød 1 [mm] 300 100 50 10 10 50 50 100 100 500 1 000 5 000 [l/s] 500 1 000 q 5 00010 000 [m³/h] Measurement function By measuring the pressure difference, Dp, between the measurement nozzles, you can derive the flow in the duct by means of the equation on the units plate. Measurement accuracy If the velocity profile is asymmetric, the measurement values can differ from the ideal values. For this reason, the flow me- ter should never be located right up to any flow disturbance. The method error in the table below will differ, depending on the distance to the flow disturbance. l 1 =straight distance before meter Type of disturbance A 90° bend Method error m 2 5% 10% 6·d 1 0·d 1 l 1 A branch l 1 Ød 1 l 2 = straight distance after meter 6·d 1 4·d 1 1·d 1 1·d 1 DUCT-MC Identification number 17.11.002 Lindab reserves the right to make changes without prior notice 2 2020-09-10