lindab | dampers and measure units Damper with flow meter DIRVU Technical data for the motor Power supply. Power consumption . For wire sizing . Connection . Operating angle. Torque at rated voltage . Direction of rotation. Position indication . Running time for 95° . Sound power level. Protection class. Protection type . Ambient temperature range . Ambient moisture . LM 24 A-SR AC 24 V, 50/60 Hz DC 24 V 1 W 2 VA Cable 1 m, 4×0,75 mm 2 Max. 95°, adjustable 0–100% Min. 5 Nm Switch selectable 0 or 1 Mechanical 150 s Max. 35 dB (A) III Safety extra-low voltage IP 54 -30 to +50°C 95 % RF – + Y U 1 2 3 5 DC 0–10 V DC 2–10 V DUCT-MC Lindab reserves the right to make changes without prior notice 2 Identification number 17.11.002 2020-09-10
Download PDF file