lindab | we simplify construction Active chilled beam Solus Use Lindab Solus is specially designed as a combined HTC and LTH beam—High Temperature Cooling and Low Temperature Heating. Due to the customized coil, the Solus beam delivers an outstanding cooling and heat- ing effect per degree temperature difference between the water circuit and the room temperature. This means that you get great capacities, at a relatively high running temperature. All in all, the Solus beam can save a lot of the energy cost on cooling and heating. Installation Solus I-60 is installed into a false ceiling, and can be suspended by hangers or threaded rods. As standard Solus is delivered for a 600 x 600 T24 false ceiling. Solus can also be delivered with a variety of dif ferent Clip-in options, making the beam suitable for other types of false ceilings. Worth noting The Angled Nozzle system secures a perfect air spread pattern, available in a number of factory preset angles. Cost saving high output beam that delivers an excellent capacity for both cooling and heating, while running the same temperature set for both functions. Pressure authority in the beam means that regulation of the air pressure is a fast and easy task. Lindabs active chilled beams are Eurovent-certified and tested according to EN-15116. Key figures Length: Width: Height: Capacity: 1800, 2400, 3000, 3600 mm 600 mm (ceiling adaption available) 200 mm Cooling: 1120 W Heating: 460 W Calculation setup Room temp: 25°C/21°C, Water temp: 20-23°C/23-22°C, Air temp: 20°C/23°C, Nozzle air pressure: 100 Pa, Air flow: 15 l/s/m. 2 Lindab reserves the right to make changes without prior notice 2021-09-15