lindab | we simplify construction Active chilled beam Premax Use Lindab's active chilled beam Premax can be used for cooling, heating and ventilation. Water valves, actuators, Regula Secura, Regula Combi and Regula Connect can all be built into the Premax beam. Installation Premax I-60 is installed into a false ceiling, and can be suspended by hangers or threaded rods. As standard Premax is delivered for a 600 x 600 T24 false ceiling. Premax can also be delivered with a variety of dif- ferent Clip-in options, making the beam suitable for other types of false ceilings. Worth noting Premax features the Lindab JetCone, an innovative way of regulating the air volume. The air volume can easily be adjusted without having to worry about pressure and noise issues. The Angled Nozzle system secures a perfect air spread pattern, available in a number of factory preset angles. As a plus feature the Lindab AirGuide system offers read- justable air spread pattern control. The beam can be easily integrated/used in a Pascal water system to enable VAV/DCV. Lindabs active chilled beams are Eurovent-certified and tested according to EN-15116. Key figures Length: Width: Height: Capacity: 1200 - 3600 mm (steps of 600 mm) 600 mm (ceiling adaption available) 200 mm 2068 W Calculation setup Room temp: 25°C, Water temp: 14-17°C, Air temp: 18°C, Nozzle air pressure: 80 Pa, Air flow: 15 l/s/m. 2 Lindab reserves the right to make changes without prior notice 2020-11-16