lindab | air valves Valve KIR Technical data Without sector plate Air flow, q [l/s] and [m 3 /h], total pressure drop, Δ p t [Pa], throw length, l 0,2 [m], and A-weighted sound power level, L WA [dB], for different settings, a [mm], are shown in the graphs. Maximal vertical width, b v [m] and Maximal horisontal width, b h [m], are shown in the tables. Sound power level, L Wok [dB], in octave bands is calculated as L WA + K ok . K ok is found in the table below. Ød Valve nom mounted in Centre frequency [Hz] 63 125 250 500 1K 2K 4K 8K 100 Duct – -6 -2 -3 -5 -8 -9 -15 125 Duct – 0 1 -1 -5 -15 -21 -33 160 Duct – 3 2 -1 -6 -15 -23 -36 Tolerance – ±3 ±2 ±2 ±2 ±2 ±2 ±3 Sound attenuation, Δ L, [dB] Ød Valve nom mounted in Centre frequency [Hz] 63 125 250 500 1K 2K 4K 8K 100 Duct 22 18 13 11 9 8 7 8 125 Duct 20 16 11 9 9 7 6 5 160 Duct 18 14 10 9 9 7 6 6 Tolerance ±6 ±3 ±2 ±2 ±2 ±2 ±2 ±3 Measurement of air flow Data is available in a separate brochure. Air jet diffusion pattern Maximal vertical width, b v [m]: Ø 100 2 200 2,0 100 l 0,2 [m] 1,5 1,0 50 Δ p t [Pa] 20 a [mm] 4 6 2,5 9 12 40 35 30 L WA [dB(A)] 10 5 20 Ø 125 200 100 50 20 10 20 30 40 50 [l/s] 50 100 180 [m 3 /h] q 4 6 3,5 3,0 2,5 a [mm] 9 12 15 2,0 l 0,2 [m] 1,5 40 35 30 L WA [dB(A)] Δ p t [Pa] 10 5 20 Ø 160 200 100 50 20 10 l 0,2 [m] 1,5 20 30 40 50 50 100 200 q 80 [l/s] [m 3 /h] 4 6 2,5 3,0 a [mm] 10 15 20 2,0 40 35 30 L WA [dB(A)] Δ p t [Pa] 10 10 40 15 20 30 40 50 100 200 q 100 130 [l/s] 300 400 [m 3 /h] 2 Lindab reserves the right to make changes without prior notice 2020-11-11