Valve lindab | air valves KIR Technical data Without sector plate Air flow, q [l/s] and [m3/h], total pressure drop, Δpt [Pa], throw length, l0,2 [m], and A-weighted sound power level, LWA [dB], for different settings, a [mm], are shown in the graphs. Maximal vertical width, bv [m] and Maximal horisontal width, bh [m], are shown in the tables. Sound power level, LWok [dB], in octave bands is calculated as LWA + Kok. Kok is found in the table below. Air jet diffusion pattern 1 Maximal vertical width, bv [m]: Setting Supply air temperature difference 2 a Δt [mm] 4 12 ±0 °C -10 °C bv = 0,04 · l02 bv = 0,064 · l02 3 bv = 0,04 · l02 bv = 0,075 · l02 4 bv 5 Ød Valve nom mounted in Centre frequency [Hz] Maximal horisontal width, bh [m]: 100 Duct 63 125 250 500 1K 2K 4K 8K – -6 -2 -3 -5 -8 -9 -15 Setting Supply air temperature difference 6 a Δt 125 Duct – 0 1 -1 -5 -15 -21 -33 [mm] ±0 °C -10 °C 160 Duct – 3 2 -1 -6 -15 -23 -36 4 bh = 2 · l02 bh = 2 · l02 7 12 bh = 2 · l02 bh = 2 · l02 Tolerance – ±3 ±2 ±2 ±2 ±2 ±2 ±3 8 Sound attenuation, ΔL, [dB] Ød Valve nom mounted in Centre frequency [Hz] 63 125 250 500 1K 2K 4K 8K 100 Duct 22 18 13 11 9 8 7 8 125 Duct 20 16 11 9 9 7 6 5 160 Duct 18 14 10 9 9 7 6 6 Tolerance ±6 ±3 ±2 ±2 ±2 ±2 ±2 ±3 bh 9 10 l0,2 11 Measurement of air flow 12 Data is available in a separate brochure. 13 14 15 16 17 18 We reserve the right to make changes without prior notice 2014-03-07